Goodman Mfg PC50 Manuel d'utilisateur Page 3

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 8
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 2
P
RODUCT
S
PECIFICATIONS
SS-PC50 www.goodmanmfg.com 3
SPECIFICATIONS
PC048-5 PC060-5
Cooling Capacity
Total BTU/h 46,400 54,700
Sensible BTU/h 33,300 39,400
SEER / EER 11.9 / 10.2 10.9 / 9.4
Decibels 80 80
Evaporator Motor
Type DD DD
Wheel (D x W) 9 x 8 10 x 8
Nominal Cooling CFM 1,365 1,693
No. of Speeds 2 2
Horsepower - RPM 1/2 - 1075 3/4 - 1075
Evaporator Coil
Face Area (ft²) 6.2 7.0
Rows Deep/ Fins per Inch 4/14 4/14
Filter Size (ft²) (2) 20 x 20 x 1 (2) 20 x 20 x 1
Drain Size (NPT) 3/4” 3/4”
Refrigerant Charge (oz.) 126 125
Condenser Fan / Coil
Horsepower - RPM 1/4 - 1075 1/4 - 1075
Fan Diameter/ # Fan Blades 22 / 4 22 / 4
Face Area (ft²) 17.8 19.1
Rows Deep/ Fins per Inch 2 / 16 2 / 16
Electrical Data
Voltage/Phase/ Frequency 380-415 / 3 / 50
Compressor RLA/LRA 7.4 / 50 10.3 / 65
Indoor Blower FLA 1.4 2.2
Outdoor Fan RLA 0.8 1.2
Total Unit Amps 8.9 11.4
Min. Circuit Ampacity ¹ 11.5 16.3
Max. Overcurrent Protection ² 20 amps 20 amps
Ship Weight (lbs) 400 400
¹ Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
² May use fuses or HACR-type circuit breakers of the same size as noted.
Note: Always check the S&R plate for electrical data on the unit being installed.
Vue de la page 2
1 2 3 4 5 6 7 8

Commentaires sur ces manuels

Pas de commentaire